SOLARCALCKIT SUITE / Dimensionado de baterías solares

Dimensionado de baterías solares

IEEE 485 & NEC 706 REFERENCE METHODOLOGY

Dimensionado determinista del banco de baterías a partir del consumo diario, la autonomía, la tensión del sistema y la química — con esquema SVG en vivo y contabilidad de pérdidas transparente.

Input Parameters
Client-Side Engine
01 Load Demand & Autonomy

Total energy all loads consume in 24 hours, in kWh/day.

Days the bank sustains loads with no solar recharge (fractions allowed).

02 System & Chemistry

Nominal DC bus voltage.

Sets recommended depth of discharge default.

03 Individual Battery Specs

Must divide system voltage exactly.

Rated nominal capacity of one unit, in Ah.

04 Losses & Depth of Discharge

Usable % of nominal capacity. Left blank uses chemistry default.

DC→AC path efficiency, %. 100 for DC-coupled.

What solar battery sizing means

Solar battery sizing answers two questions at once: how much energy your battery bank must store, and how that energy must be arranged as physical batteries. The energy side is set by your daily consumption, your autonomy requirement, your inverter's efficiency, and the depth of discharge your chemistry tolerates. The physical side is a series-and-parallel arrangement that reaches your system voltage and amp-hour target using whole batteries.

Methodology

The four-step sizing math

Every number this calculator produces follows from these four transparent steps — no hidden margins.

Step 1 · Autonomy energy

E_autonomy = daily energy × autonomy days

Total load energy consumed over the autonomy window with no solar recharge.

Step 2 · Terminal Energy

E_usable = E_autonomy ÷ inverter efficiency

Accounts for DC→AC conversion losses in the inverter (typically 90%).

Step 3 · Nominal Capacity

E_nominal = E_usable ÷ depth of discharge

DoD is the usable fraction (80% LiFePO4, 50% Lead-Acid) to protect battery cycle life.

Step 4 · Series / Parallel Topology

series = V_sys ÷ V_bat · strings = ⌈req Ah ÷ bat Ah⌉

Series multiplies voltage; parallel multiplies capacity. Strings round up to prevent undersizing.

Assumptions

What is — and is not — modeled

Modeled explicitly

Daily load energy, autonomy, inverter (DC→AC) path efficiency, and usable depth of discharge. Nominal energy, usable energy, and required capacity are reported separately.

Deliberately not modeled

Battery round-trip losses and aging margins are not applied as hidden multipliers. Temperature derating is not assumed — keep margin for extreme cold.

Preguntas frecuentes

¿Cuántas baterías necesito para un sistema solar de 24 V?

Depende de tu consumo diario y de la autonomía. Con baterías de 12 V en un sistema de 24 V, se conectan dos en serie por cadena, y las cadenas en paralelo son los amp-horas necesarios divididos entre los Ah de una batería, redondeando hacia arriba. Ejemplo: 5 kWh/día con 1 día de autonomía en LiFePO4 requiere unos 289 Ah a 24 V — tres cadenas paralelas de 100 Ah, 6 baterías de 12 V 100 Ah (2S3P) en total.

¿Qué diferencia hay entre conexión en serie y en paralelo?

La serie suma tensión: dos baterías de 12 V 100 Ah en serie dan 24 V a 100 Ah. El paralelo suma capacidad: las mismas dos en paralelo dan 12 V a 200 Ah. Los bancos usan baterías idénticas en serie hasta la tensión del sistema y cadenas idénticas en paralelo hasta los amp-horas requeridos.

¿Qué profundidad de descarga debo usar?

Usa el valor que tu química soporte con regularidad: 80% para LiFePO4 y litio NMC, 50% para AGM, gel y plomo-ácido inundado. Más profundidad significa más capacidad útil por ciclo pero menor vida útil — consulta la ficha técnica de tu batería.