SOLARCALCKIT SUITE / 태양광 배터리 설계 도구

태양광 배터리 설계 도구

IEEE 485 & NEC 706 REFERENCE METHODOLOGY

일일 에너지, 무독립 일수, 시스템 전압, 화학 성분으로 결정론적으로 배터리 뱅크를 설계 — 라이브 SVG 토폴로지 도식과 투명한 손실 계산 포함.

Input Parameters
Client-Side Engine
01 Load Demand & Autonomy

Total energy all loads consume in 24 hours, in kWh/day.

Days the bank sustains loads with no solar recharge (fractions allowed).

02 System & Chemistry

Nominal DC bus voltage.

Sets recommended depth of discharge default.

03 Individual Battery Specs

Must divide system voltage exactly.

Rated nominal capacity of one unit, in Ah.

04 Losses & Depth of Discharge

Usable % of nominal capacity. Left blank uses chemistry default.

DC→AC path efficiency, %. 100 for DC-coupled.

What solar battery sizing means

Solar battery sizing answers two questions at once: how much energy your battery bank must store, and how that energy must be arranged as physical batteries. The energy side is set by your daily consumption, your autonomy requirement, your inverter's efficiency, and the depth of discharge your chemistry tolerates. The physical side is a series-and-parallel arrangement that reaches your system voltage and amp-hour target using whole batteries.

Methodology

The four-step sizing math

Every number this calculator produces follows from these four transparent steps — no hidden margins.

Step 1 · Autonomy energy

E_autonomy = daily energy × autonomy days

Total load energy consumed over the autonomy window with no solar recharge.

Step 2 · Terminal Energy

E_usable = E_autonomy ÷ inverter efficiency

Accounts for DC→AC conversion losses in the inverter (typically 90%).

Step 3 · Nominal Capacity

E_nominal = E_usable ÷ depth of discharge

DoD is the usable fraction (80% LiFePO4, 50% Lead-Acid) to protect battery cycle life.

Step 4 · Series / Parallel Topology

series = V_sys ÷ V_bat · strings = ⌈req Ah ÷ bat Ah⌉

Series multiplies voltage; parallel multiplies capacity. Strings round up to prevent undersizing.

Assumptions

What is — and is not — modeled

Modeled explicitly

Daily load energy, autonomy, inverter (DC→AC) path efficiency, and usable depth of discharge. Nominal energy, usable energy, and required capacity are reported separately.

Deliberately not modeled

Battery round-trip losses and aging margins are not applied as hidden multipliers. Temperature derating is not assumed — keep margin for extreme cold.

자주 묻는 질문

24V 태양광 시스템에 배터리가 몇 개 필요한가요?

일일 전력 사용량과 무독립 일수에 따라 다릅니다. 24V 시스템에서 12V 배터리를 쓰면 스트링당 2개를 직렬로 연결하고, 병렬 스트링 수는 필요한 암페어시를 배터리 1개의 암페어시로 나누어 올림합니다. 예: LiFePO4에서 5kWh/일, 1일 무독립이면 24V에서 약 289Ah 필요 — 100Ah 병렬 3스트링, 12V 100Ah 배터리 6개(2S3P)입니다.

직렬과 병렬 배선의 차이는 무엇인가요?

직렬은 전압을 더합니다: 12V 100Ah 배터리 2개 직렬은 24V 100Ah. 병렬은 용량을 더합니다: 같은 2개 병렬은 12V 200Ah. 뱅크는 동일 배터리를 직렬로 시스템 전압을 만든 뒤, 동일 스트링을 병렬로 필요한 암페어시를 채웁니다.

방전 심도(DoD)는 얼마로 해야 하나요?

배터리 화학 성분이 정기적으로 유지할 수 있는 값을 쓰세요: LiFePO4와 NMC 리튬은 80%, AGM·젤·액침 납축전지는 50%가 보수적 설계값입니다. 깊은 방전은 사이클당 사용 가능 용량을 늘리지만 수명을 줄입니다 — 배터리 데이터시트를 확인하세요.