태양광 전선 규격 및 전압 강하

NEC CH. 9 & IEC 60228 REFERENCE RESISTIVITY

전류, 회로 길이, 허용 전압 강하로 DC 배선을 설계 — 구리·알루미늄 저항률 표를 표준 AWG·mm² 규격에 매핑.

Circuit Parameters
Client-Side Engine
01 Circuit Demand & Length

Conductor current in amps.

One-way distance in metres (doubled for round-trip).

Nominal DC circuit voltage.

Standard practice is ≤3% for DC solar cable runs.

02 Conductor Material & Specific Check

Uses standard 20 °C resistivity values.

Enter standard mm² size to check its exact voltage drop.

How solar wire size is determined

A DC solar cable has to carry current without overheating (ampacity) and without wasting too much voltage (voltage drop). This solar wire size calculator sizes for voltage drop, which drives the cross-section for most solar runs.

Formulas

The voltage-drop math

Three deterministic equations from Ohm's Law and conductor resistivity.

Step 1 — Round-Trip Resistance

R = (2 × L × ρ) ÷ Area

Round-trip length (2 × L) accounts for positive and negative conductors.

Step 2 — Voltage Drop

V_drop = I × R  ·  Drop% = (V_drop ÷ V_sys) × 100

Voltage lost as heat across the conductor run.

자주 묻는 질문

태양광 DC 배선에서 허용 전압 강하는 얼마인가요?

대부분의 설계자는 DC 스트링과 배터리 케이블에서 2% 이하, 전체에서 3%를 넘지 않도록 목표합니다. 과도한 강하는 열로 에너지를 낭비하고 배터리가 완충 전압에 도달하지 못하게 할 수 있습니다.

전선 길이는 단방향으로 셀까요 왕복으로 셀까요?

DC 회로는 두 도체 모두에서 전압을 잃으므로 계산은 왕복 전체 거리를 사용합니다. 단방향 길이를 입력하면 계산기가 2배로 하고, 또는 회로 총 길이를 직접 입력할 수 있습니다.

태양광에는 구리와 알루미늄 중 무엇을?

구리는 알루미늄보다 약 60% 더 잘 전도하므로 알루미늄은 같은 강하에 더 큰 단면적이 필요합니다 — 하지만 긴 구간에서는 더 저렴하고 가볍습니다. 단자 하드웨어는 항상 사용 도체 금속에 맞는 정격이어야 합니다.