SOLARCALCKIT SUITE / 太陽光用電線サイズと電圧降下

太陽光用電線サイズと電圧降下

NEC CH. 9 & IEC 60228 REFERENCE RESISTIVITY

電流・回路長・許容電圧降下からDC配線を設計 — 銅・アルミの抵抗率表をAWG・mm²標準規格にマッピング。

Circuit Parameters
Client-Side Engine
01 Circuit Demand & Length

Conductor current in amps.

One-way distance in metres (doubled for round-trip).

Nominal DC circuit voltage.

Standard practice is ≤3% for DC solar cable runs.

02 Conductor Material & Specific Check

Uses standard 20 °C resistivity values.

Enter standard mm² size to check its exact voltage drop.

How solar wire size is determined

A DC solar cable has to carry current without overheating (ampacity) and without wasting too much voltage (voltage drop). This solar wire size calculator sizes for voltage drop, which drives the cross-section for most solar runs.

Formulas

The voltage-drop math

Three deterministic equations from Ohm's Law and conductor resistivity.

Step 1 — Round-Trip Resistance

R = (2 × L × ρ) ÷ Area

Round-trip length (2 × L) accounts for positive and negative conductors.

Step 2 — Voltage Drop

V_drop = I × R  ·  Drop% = (V_drop ÷ V_sys) × 100

Voltage lost as heat across the conductor run.

よくある質問

太陽光DC配線で許容できる電圧降下は?

多くの設計者はDCストリングやバッテリーケーブルで2%以下、全体でも3%以内を目標にします。過大な降下は熱としてエネルギーを浪費し、バッテリーが満充電電圧に達しなくなることがあります。

ケーブル長は片道?往復?

DC回路は両方の導体で電圧を失うため、計算には往復の全距離を使います。片道距離を入力すれば計算ツールが2倍します(往復の全長を直接入力しても構いません)。

太陽光には銅とアルミどちら?

銅はアルミより約60%よく導電するため、同じ降下にはアルミは大きな断面積が必要です — ただし長距離では安価で軽量です。接続端子は使用する導体金属に適合する定格である必要があります。